Global Global Algérie Français Algeria English Angola Português Angola English Argentina Español Argentina English Australia English Austria Deutsch Austria English Azerbaijan English Azerbaijan Русский Bahrain English Bangladesh English Belgium English Belgium Français Belgium Nederlands Brazil Português Brazil English Bulgaria български Bulgaria English Cameroon English Cameroon Français Canada English Canada Français Chile Español Chile English China 中文 China 日本語 China English Colombia Español Colombia English Croatia English Czech Republic Čeština Czech Republic English Denmark English Djibouti English Ecuador Español Ecuador English Egypt English Estonia English Ethiopia English Finland Suomi Finland English France Français France English Georgia English Georgia Русский Germany Deutsch Germany English Ghana English Greece Ελληνικά Greece English Guatemala Español Guatemala English Hong Kong, China English Hong Kong, China 中文 Hungary Magyar Hungary English India English Indonesia English Iraq English Ireland English Italy Italiano Italy English Ivory Coast Français Ivory Coast English Japan 日本語 Japan English Jordan English Kazakhstan Русский Kazakhstan English Kenya English Kuwait English Kyrgyzstan Русский Kyrgyzstan English Latvia English Lithuania English Malaysia English Mauritius English Mauritius français (Maurice) Mexico Español Mexico English Moldova Română Moldova English Mongolia English Morocco English Morocco Français Mozambique Português Mozambique English Netherlands Nederlands Netherlands English New Zealand English Nigeria English Norway English Oman English Pakistan English Paraguay Español Paraguay English Peru Español Peru English Philippines English Poland Polski Poland English Portugal Português Portugal English Qatar English Republic of Korea 한국어 Republic of Korea English Romania Română Romania English Saudi Arabia English Serbia Српски Serbia English Singapore English Slovakia English Slovenia English South Africa English Spain English Spain Español Sri Lanka English Sweden English Switzerland Deutsch Switzerland Français Switzerland Italiano Switzerland English Tanzania English Thailand ไทย Thailand English Togo English Togo Français Tunisia English Tunisia Français Türkiye Türkçe Türkiye English Turkmenistan Русский Turkmenistan English Ukraine Українська Ukraine English United Arab Emirates English United Kingdom English Uruguay Español Uruguay English USA English Uzbekistan English Uzbekistan Русский Vietnam Tiếng Việt Vietnam English

Chemical anchor tensile resistance testing is the essential qualification and acceptance procedure used to verify that bonded anchor systems can safely transfer design pull-out loads in concrete and masonry structures. This guide explains the relevant international and national standards (EN 1992-4, EAD 330499, ASTM E488, ACI 355.4, GB 50367, JGJ 145), sample requirements, test items, laboratory and on-site test methods, failure mode evaluation, and typical acceptance criteria, providing engineers and QA professionals with a practical technical reference.

Technical Overview

Chemical anchors, also known as bonded or adhesive anchors, are post-installed fastening systems in which a two-component thermosetting adhesive, typically vinylester, polyester, epoxy acrylate or pure epoxy, bonds a threaded rod or deformed reinforcing bar to the wall of a drilled hole in concrete or masonry. Because load transfer is achieved through chemical adhesion and mechanical interlock rather than expansion force, chemical anchors generate no installation stress in the base material and are suitable for applications with small edge distances, narrow member thicknesses and heavy sustained loads.

The tensile resistance test is the principal qualification and acceptance test for these systems. It determines the ultimate pull-out capacity, the load-displacement behaviour, the characteristic bond resistance and the governing failure mode of the anchor assembly under axial tension. Test results feed directly into design calculations, European Technical Assessments, product certifications and job-site acceptance decisions.

Purpose of Tensile Testing

  • To establish the ultimate and characteristic tensile resistance of a bonded anchor system for a given diameter, embedment depth and base material strength
  • To verify performance in cracked and uncracked concrete, including sensitivity to crack width and crack movement
  • To quantify long-term behaviour under sustained tensile load (creep) and at elevated service temperatures
  • To confirm correct installation practice, including hole cleaning, injection technique, installation direction and cure time
  • To provide documentary evidence for structural design, product approval and on-site quality acceptance

Governing Standards and Reference Documents

  • EN 1992-4, design of fastenings for use in concrete, which defines the required characteristic resistances derived from testing
  • EAD 330499, the European Assessment Document for bonded fasteners for use in concrete, which superseded ETAG 001 Part 5 and specifies the full qualification test programme
  • ASTM E488/E488M, standard test methods for strength of anchors in concrete elements, widely applied in North America
  • ACI 355.4, qualification of post-installed adhesive (bonded) anchors in concrete, with design rules given in ACI 318, Chapter 17
  • EN 1504-6, covering products and systems for anchoring of reinforcing steel bar by structural bonding
  • GB 50367, the Chinese code for design of strengthening of concrete structures, which regulates post-installed anchorage in strengthening works
  • JGJ 145, the Chinese technical specification for post-installed fastenings in concrete, including on-site inspection procedures
  • ISO/IEC 17025, governing the technical competence of accredited third-party laboratories that perform these tests

Testing Samples

Resin Capsule (Ampoule) Anchor Systems

Capsule systems consist of pre-measured glass ampoules or foil packs containing resin and hardener. The threaded rod is driven and rotated into the capsule with a rotary hammer drill, crushing the container and mixing the components in the hole. Typical sample configurations range from M8 to M32 rod diameters with effective embedment depths of approximately 4 to 10 rod diameters.

Injection Adhesive Anchor Systems

Injection systems use side-by-side or coaxial cartridges with a static mixing nozzle. The adhesive is dispensed from the bottom of the cleaned drill hole with progressive withdrawal, and the rod is inserted with a rotating motion. Sample kits submitted for testing include the adhesive cartridges, mixing nozzles, dispensing tool, brushes and blow pumps specified in the manufacturer's printed installation instructions.

Anchor Elements

Anchor elements include cut-to-length threaded rods in property classes 5.8 and 8.8 with hot-dip galvanized or zinc-electroplated coatings, stainless steel rods in grades A2-70 and A4-70, and deformed reinforcing bars for post-installed rebar connections. Nuts and washers accompanying each rod type are tested as part of the complete assembly.

Base Material Specimens

Laboratory tests are performed on concrete slabs or blocks with a defined strength class, commonly between C20/25 and C50/60 per EN 206, and a member thickness sufficient to prevent splitting, typically at least 1.5 times the effective embedment depth. Specimens are cast for both uncracked and cracked conditions; cracked specimens contain induced cracks of nominally 0.3 mm width through the anchor position. Conditioning of specimens and anchors to the standard laboratory climate (20 ± 3) °C is required unless a specific temperature test is being performed.

Testing Items

Depending on the qualification scope and project requirements, the following test items are typically performed:

  • Ultimate tensile capacity in uncracked concrete (reference tests)
  • Ultimate tensile capacity in cracked concrete, including crack cycling sensitivity
  • Characteristic bond resistance, calculated as the 5% fractile with a stated confidence level
  • Load-displacement behaviour, including displacement at defined load levels and anchor stiffness
  • Sustained load (creep) tests, with displacement extrapolation to the design service life
  • Tensile tests at maximum long-term and short-term service temperatures
  • Installation sensitivity tests, covering hole cleanliness, overhead and horizontal installation, and installation at extreme ambient temperatures
  • Durability-related tests after exposure to alkaline solution, freeze-thaw cycles and wetting-drying cycles
  • Seismic qualification tests for performance categories C1 and C2 where applicable
  • On-site non-destructive proof load tests and destructive verification tests for job acceptance

Testing Methods

Specimen Preparation and Installation

Test holes are drilled with a hammer drill using the nominal drill bit diameter specified for the anchor. Holes are cleaned according to the manufacturer's printed installation instructions, typically using a blow-brush-blow sequence. Anchors are installed in the specified orientation (downward, horizontal or overhead), and the adhesive is allowed to cure for the datasheet cure time at the recorded ambient temperature before loading. All installation parameters, including drill diameter, embedment depth, cleaning procedure, resin batch and temperature, are documented, because these variables have a direct influence on bond resistance.

Reference Tension Tests in the Laboratory

Reference tests are carried out on a calibrated universal testing machine or a hydraulic pull-testing rig with a calibrated load cell and displacement transducers. Two configurations are distinguished:

  • Unconfined tension test: the reaction frame support is positioned far enough from the anchor, commonly at least two effective embedment depths, so that a concrete breakout cone can develop freely. This configuration reproduces real structural behaviour.
  • Confined tension test: a restraint plate near the anchor suppresses concrete breakout, isolating the bond and pull-out behaviour of the adhesive itself.

Loading is applied monotonically at a controlled rate such that ultimate load is reached within the time window required by the applicable standard, typically one to three minutes, or in defined load steps with displacement recorded at each increment. Displacement is measured with LVDT transducers mounted on a reference frame that is mechanically independent of the loading fixture. The ultimate load, the complete load-displacement curve and the observed failure mode are recorded for every specimen.

Evaluation of Results and Failure Modes

For each test series, the mean ultimate load, the coefficient of variation and the characteristic resistance are calculated. Average ultimate bond stress is evaluated as the ultimate load divided by the cylindrical bond area, that is, the product of Pi, the drill hole diameter and the effective embedment depth. Characteristic values are determined as the 5% fractile at a defined confidence level. The governing failure mode must be documented and typically falls into one of the following categories:

  • Steel failure of the rod or bar, which is the preferred and most ductile mode for heavily loaded anchors
  • Pull-out failure by debonding at the adhesive-to-concrete interface
  • Pull-through failure, in which the rod pulls through the adhesive body
  • Concrete cone (breakout) failure, with or without partial bond failure at the interface
  • Splitting failure of the base member, which usually indicates unsuitable member geometry or spacing

Sustained Load (Creep) Testing

Because polymer adhesives are viscoelastic, anchors are subjected to a sustained tensile load for a minimum duration, commonly 42 days, at the maximum long-term service temperature. Displacement is logged continuously or at defined intervals and extrapolated to the 50-year design life. Acceptance criteria limit the creep factor and the projected long-term displacement, ensuring that the anchor will not undergo excessive creep deformation or delayed failure under permanent load.

Cracked Concrete and Temperature Tests

Cracked-concrete tests are performed with cracks of nominal width 0.3 mm passing through the anchor, and may include cyclic crack opening and closing as well as repeated loading to simulate service conditions in reinforced concrete structures in tension. Temperature tests are conducted at the declared maximum short-term and long-term service temperatures of the product, and reduced-temperature tests verify handling and curing behaviour at low ambient conditions.

On-Site Proof Load Testing

For project acceptance, non-destructive proof tests are performed with a calibrated portable hydraulic pull tester and a reaction frame with adequate clearance to avoid restraining the concrete. The anchor is loaded in increments up to the specified proof load, commonly in the range of 1.3 to 1.5 times the design tensile load, and the load is held for a specified dwell time, typically 30 to 60 seconds. Acceptance requires that the anchor sustains the proof load without failure, slipping or disproportionate increase in displacement. Destructive verification tests on sampled anchors are used where the specification requires statistical confirmation of the characteristic resistance of the installed population.

Applications

Chemical anchor tensile testing supports a wide range of construction and engineering applications:

  • Structural steel-to-concrete connections, including column base plates, beam seats, brackets and machine foundations
  • Post-installed reinforcing bar connections for new openings, wall extensions and slab junctions
  • Strengthening and retrofitting of existing concrete structures in accordance with GB 50367 and related design codes
  • Curtain wall, facade and guardrail bracket anchoring on high-rise buildings
  • Infrastructure works, including tunnels, bridges, railway fixings, noise barriers and highway safety systems
  • Anchoring in zones of reinforced concrete tension, where cracked-concrete performance is mandatory
  • Seismic retrofitting in regions with moderate to high seismic demand
  • Equipment anchoring subject to vibration, fatigue or sustained tensile loading

FAQ

What is the difference between a confined and an unconfined tension test?

A confined test uses a restraint plate that prevents concrete breakout, so the measured capacity reflects the bond strength of the adhesive. An unconfined test allows a concrete cone to form and therefore reproduces the behaviour expected in a real structure. Qualification programmes typically require both configurations for different purposes.

How is the characteristic bond resistance determined?

The individual ultimate loads of a test series are statistically evaluated. The mean value and coefficient of variation are computed, and the characteristic resistance is taken as the 5% fractile at a defined confidence level. Series with excessive scatter, for example a coefficient of variation above the limit stated in the assessment document, are normally rejected or require additional testing.

Can an on-site tested anchor remain in service afterwards?

Anchors subjected to non-destructive proof loading within the specified proof load level may generally remain in service, provided no displacement anomalies are observed. Anchors loaded to destruction must obviously be replaced or re-installed, and their positions should be recorded.

How long must the adhesive cure before testing?

The cure time printed in the manufacturer's installation instructions for the actual ambient and base-material temperature must be respected. Depending on the adhesive chemistry and temperature, this can range from under one hour for fast-curing vinylesters to many hours, or even a full day, for slow-curing epoxies.

Why is testing in cracked concrete required?

In reinforced concrete structures subject to bending or tension, cracks with widths of about 0.3 mm can pass through anchor positions and significantly reduce bond resistance. Testing with defined crack widths and crack movement demonstrates that the anchor remains safe under these realistic service conditions.

Which failure mode indicates a correctly designed installation?

Steel failure of the anchor rod is the preferred mode because it is predictable and ductile. Pull-out or bond failure is acceptable provided the measured characteristic resistance exceeds the design requirement. Splitting of the concrete or unexplained scatter in results usually indicates installation deficiencies or unsuitable detailing.

Who should perform these tests?

Qualification and product-certification testing should be carried out by accredited third-party laboratories with calibrated equipment and documented competence under ISO/IEC 17025. On-site proof tests may be performed by trained site technicians using calibrated devices under the supervision of the project engineer or a qualified inspection body.